A new generation of engineers has realized they can push heat pumps to the limit.

    • LengAwaits@lemmy.world
      link
      fedilink
      arrow-up
      2
      ·
      edit-2
      4 months ago

      At the time of writing, real-time data suggests that for every kilowatt-hour of electricity Ritchie’s heat pump consumes, it delivers 5.5 kilowatt-hours of heat—a coefficient of performance, or COP, of 5.5.

      • Kairos@lemmy.today
        link
        fedilink
        arrow-up
        1
        arrow-down
        1
        ·
        4 months ago

        You can easily almost double that if you’re willing to break the pump in a few years.

        But usually that’s more expensive per BTU/other heat unit because the pumps are expensive. That’s why I asked.

        • evranch
          link
          fedilink
          arrow-up
          5
          ·
          4 months ago

          Double would be a COP of over 10. That’s a stretch for an overbuilt GSHP and not even slightly feasible for air-air.

          High COPs are usually easy on a compressor as they represent low compression ratios and low differential temps. For example I can hit around COP 7 in cooling on my scrap heap GSHP, with an evap temp around 10C and condenser temp around 20C. That’s a high side pressure around 100 psi and only 30 psi of differential, “barely working” as far as the compressor is concerned.

          The only way I know to get high COPs is to have an oversized condenser and a way to get your refrigerant below ambient, like evaporative, ground source or overnight radiant so you can get the compression ratio down, unless you know a secret in which case I’m not afraid to burn out a compressor or two trying it out!

          • Kairos@lemmy.today
            link
            fedilink
            arrow-up
            2
            arrow-down
            1
            ·
            4 months ago

            I don’t rember the details of how it works. I think it just reduces the torque or something? Maybe it doesn’t work on newer pumps or they already do it.

            • evranch
              link
              fedilink
              arrow-up
              4
              ·
              4 months ago

              Oh I think I know what you’re talking about, abusing a minisplit by idling the inverter back too far. Effectively you have a hugely oversized condenser for the tiny flow, under the right conditions like a cool night you can get ridiculous subcooling.

              But COP is irrelevant in this case because you’ve derated the actual BTU to near zero, you aren’t moving any refrigerant.

              Also yes this will kill your compressor because the minimum speed is set where it will get enough oil flow. Run it too slow, and it won’t pick up oil and eventually seize up. You also could end up running the suction in vacuum which is also hard on compressors.